Calculate liquid static pressure produced by a vertical fluid column.
Why it matters: Elevation pressure affects fill settings, gauge readings, equipment ratings, and pressure relationships throughout a building.
ΣCALCULATE · VERIFY · INTERPRET
Calculated result
Engineering evaluation
Calculation complete
Liquid-column static pressure (Pstatic)43.35 psi
Vertical liquid head (h)
100 ft
Fluid specific gravity (SG)
1 ratio
Engineering interpretation
A 100 ft column of fluid with specific gravity 1 produces approximately 43.35 psi of static pressure.
Important limitations
This is a hydrostatic relationship. It does not include pump head, friction, thermal expansion, transient pressure, or required operating margin.
Engineering knowledge center
Understand the calculation—not just the answer
2026-08-07 · Free Library
Governing relationships
Pstatic = 0.4335275·SG·h
Current substitution
Pstatic = 0.4335275×1×100 = 43.35 psi.
Calculation sequence
Step-by-step method
Confirm the vertical height rather than total pipe length.
Confirm fluid specific gravity at the evaluated temperature.
Multiply height by the selected hydrostatic pressure gradient and specific gravity.
Equation legend
Inputs and calculated quantities
h
Vertical liquid-column height — ft or m
SG
Fluid specific gravity — ratio
Pstatic
Liquid-column static pressure — psi
h
Vertical liquid head — ft
SG
Fluid specific gravity — ratio
Applications
How this calculation is used
Building design
Screen hydrostatic pressure at a building elevation.
Construction
Check whether installed components and gauges are referenced to the correct elevation.
Commissioning
Normalize pressure readings taken at different elevations.
Quality controls
Assumptions and limitations
Assumptions
Entered values describe the same stable operating condition.
Units, pressure definitions, fluid properties, and equipment boundaries are applied consistently.
Limitations
This tool supports preliminary evaluation and field verification; it does not replace manufacturer curves or project-specific engineering analysis.
Project criteria, applicable standards, measurement uncertainty, and authorized professional judgment remain controlling.
Field use
Verification procedure
Confirm the approved reference condition, instrument range, and calculation boundary.
Stabilize the system and record calibrated field measurements.
Compare the result with current manufacturer data and project requirements before disposition.
Common engineering mistakes
Mixing measurements from different operating conditions or equipment boundaries.
Treating a calculated screening status as automatic acceptance.
Technical basis
References and source standards
ASHRAE Handbook—FundamentalsCurrent handbook chapters covering fluid flow, pressure relationships, system curves, and mechanical-system fundamentals; the licensed edition must be verified during professional review.
These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.