CommissioningIntermediateHeat Transfer

Coil Capacity Verification Calculator

Calculate airside sensible coil capacity and compare it with an approved design value.

Why it matters: Capacity verification connects airflow and temperature difference to delivered performance while keeping uncertainty visible.

User inputs

Enter field measurements

8 inputs
Select the unit convention used for the engineering quantities shown on this page.
Btu/h or kWApproved sensible capacity at the intended test condition.
cfm or m³/sRepresentative measured airflow.
°F or °CRepresentative entering dry-bulb temperature.
°F or °CRepresentative leaving dry-bulb temperature.
lb/ft³ or kg/m³Air density at the average test condition.
Btu/(lb·°F) or kJ/(kg·K)Specific heat in the selected unit system.
± %Project-specific tolerance.

Calculated result

Engineering evaluation

Within entered screening criteria
Measured sensible capacity relative to schedule (PC)100 %
Calculated sensible capacity (Ccalc)
216,000 Btu/h
Measured temperature-difference magnitude (ΔT)
20 °F
Signed leaving-minus-entering temperature change (ΔTs)
-20 °F
Signed capacity deviation (δC)
0 %

Engineering interpretation

Calculated sensible capacity magnitude is 216000 Btu/h, or 100% of the entered scheduled capacity. The signed temperature change indicates cooling. This result excludes latent capacity and is sensitive to airflow, sensor placement, and small temperature differences.

Engineering knowledge center

Understand the calculation—not just the answer

2026-08-07 · Free Library
Governing relationships
ΔTs = Tl−Te
ΔT = |ΔTs|
Ccalc = 60ρcpQΔT
PC = Ccalc/Cd×100
δC = PC−100
within entered criterion when |δC| ≤ T
Current substitution

ΔTs = 55−75 = -20; ΔT = |-20| = 20; Ccalc = 60×0.075×0.24×10000×20 = 216000 Btu/h; PC = 100%.

Calculation sequence

Step-by-step method

  1. Calculate the signed leaving-minus-entering temperature change and its magnitude.
  2. Apply the sensible heat balance using entered density and specific heat.
  3. Compare measured capacity with the approved reference and entered tolerance.

Equation legend

Inputs and calculated quantities

Cd
Scheduled sensible capacity — Btu/h or kW
Q
Measured airflow — cfm or m³/s
Te
Entering dry-bulb temperature — °F or °C
Tl
Leaving dry-bulb temperature — °F or °C
ρ
Air density — lb/ft³ or kg/m³
cp
Air specific heat — Btu/(lb·°F) or kJ/(kg·K)
T
Authorized capacity tolerance — ± %
PC
Measured sensible capacity relative to schedule — %
Ccalc
Calculated sensible capacity — Btu/h
ΔT
Measured temperature-difference magnitude — °F
ΔTs
Signed leaving-minus-entering temperature change — °F
δC
Signed capacity deviation — %

Engineering calculation disclaimer

These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.