CommissioningIntermediateCentral Plant

Cooling-Tower Performance Calculator

Calculate tower range, approach, effectiveness, and deviation from an entered design approach.

Why it matters: Range and approach distinguish heat-rejection load from the tower's ability to approach ambient wet-bulb temperature.

User inputs

Enter field measurements

6 inputs
Select the unit convention used for the engineering quantities shown on this page.
°F or °CWater temperature entering the tower.
°F or °CWater temperature leaving the tower.
°F or °CRepresentative wet-bulb temperature of air entering the tower.
°F or KDesign or test-basis approach.
°F or KAllowed approach above the entered design value.

Calculated result

Engineering evaluation

Within entered screening criteria
Measured cooling-tower approach (A)7 °F
Cooling-tower range (R)
10 °F
Temperature effectiveness (E)
58.82 %
Relative approach deviation from design (informational) (δArel)
0 %

Engineering interpretation

Measured range is 10 °F, approach is 7 °F, and temperature effectiveness is 58.82%. The relative approach deviation is informational; the status color uses the entered absolute approach tolerance. Compare only at the documented flow, load, fan operation, and ambient test basis.

Engineering knowledge center

Understand the calculation—not just the answer

2026-08-07 · Free Library
Governing relationships
R = Th−Tc
A = Tc−Twb
E = R/(Th−Twb)×100
δArel = (A−Ad)/Ad×100
within entered absolute criterion when A ≤ Ad+T
Current substitution

R = 95−85 = 10 °F; A = 85−78 = 7 °F; E = 58.82%.

Calculation sequence

Step-by-step method

  1. Subtract cold-water temperature from hot-water temperature for range.
  2. Subtract entering wet bulb from cold-water temperature for approach.
  3. Compare approach with the entered design value and tolerance.

Equation legend

Inputs and calculated quantities

Th
Entering hot-water temperature — °F or °C
Tc
Leaving cold-water temperature — °F or °C
Twb
Entering-air wet-bulb temperature — °F or °C
Ad
Approved design approach — °F or K
T
Authorized approach tolerance — °F or K
A
Measured cooling-tower approach — °F
R
Cooling-tower range — °F
E
Temperature effectiveness — %
δArel
Relative approach deviation from design (informational) — %

Engineering calculation disclaimer

These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.