PlumbingIntermediateNatural and Fuel Gas

Fuel-Gas Load and Flow Calculator

Sum user-entered appliance loads and convert diversified load to ideal gas volume flow using a user-entered heating value.

Why it matters: Load inventory and heating-value conversion are distinct from pipe sizing, pressure drop, combustion, and code compliance.

User inputs

Enter field measurements

10 inputs
Select I-P or SI display units. Convert the entire input set before calculating.
countWhole-number quantity for row 1.
Btu/h or kW eachUser-entered appliance input rating.
countWhole-number quantity for row 2.
Btu/h or kW eachUser-entered appliance input rating.
countWhole-number quantity for row 3.
Btu/h or kW eachUser-entered appliance input rating.
0–1Visible approved factor; use 1.0 unless a lower value is specifically authorized.
Btu/ft³ or kWh/m³User-entered higher- or lower-heating-value basis.
Identify fuel, HHV or LHV, source, and applicable conditions.

Calculated result

Engineering evaluation

Calculation complete—verify project criteria
Ideal fuel-gas volume flow (Qᵍ)180 ft³/h
Connected appliance load (Hᶜ)
180,000 Btu/h
Diversified design load (Hᴰ)
180,000 Btu/h

Engineering interpretation

The entered load inventory represents 180000 Btu/h diversified load and 180 ft³/h ideal gas flow.

Important limitations

  • Load/flow conversion only. This tool never sizes pipe, calculates pressure drop, establishes code compliance, or selects appliances, regulators, valves, vents, combustion air, or meters. Confirm fuel, HHV/LHV, standard conditions, altitude, utility data, and diversity authorization.

Engineering knowledge center

Understand the calculation—not just the answer

2026-08-07 · Free Library
Governing relationships
Hᶜ=n₁H₁+n₂H₂+n₃H₃
Hᴰ=D·Hᶜ
Qᵍ=Hᴰ/HV
Current substitution

Hᶜ=1×100000+1×80000+0×0=180000; Hᴰ=1×180000=180000; Qᵍ=180000/1000=180 ft³/h.

Calculation sequence

Step-by-step method

  1. Sum appliance quantities times user-entered input ratings.
  2. Apply only the visible approved diversity factor.
  3. Divide by the user-entered heating value on the same HHV/LHV basis.

Equation legend

Inputs and calculated quantities

n₁
Appliance quantity row 1 — count
H₁
Appliance load row 1 — Btu/h or kW each
n₂
Appliance quantity row 2 — count
H₂
Appliance load row 2 — Btu/h or kW each
n₃
Appliance quantity row 3 — count
H₃
Appliance load row 3 — Btu/h or kW each
D
Approved diversity factor — 0–1
HV
Fuel heating value — Btu/ft³ or kWh/m³
Qᵍ
Ideal fuel-gas volume flow — ft³/h
Hᶜ
Connected appliance load — Btu/h
Hᴰ
Diversified design load — Btu/h

Engineering calculation disclaimer

These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.

Read the full use and limitation statement