Calculation sequence
Step-by-step method
- Sum appliance quantities times user-entered input ratings.
- Apply only the visible approved diversity factor.
- Divide by the user-entered heating value on the same HHV/LHV basis.
Sum user-entered appliance loads and convert diversified load to ideal gas volume flow using a user-entered heating value.
Why it matters: Load inventory and heating-value conversion are distinct from pipe sizing, pressure drop, combustion, and code compliance.
Calculated result
The entered load inventory represents 180000 Btu/h diversified load and 180 ft³/h ideal gas flow.
Engineering knowledge center
Hᶜ=1×100000+1×80000+0×0=180000; Hᴰ=1×180000=180000; Qᵍ=180000/1000=180 ft³/h.
Calculation sequence
Equation legend
Applications
Document an appliance-load and ideal-flow screen.
Check appliance quantities, input ratings, and fuel basis.
Reconcile connected input ratings without sizing gas piping or selecting equipment.
Quality controls
Field use
Technical basis
These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.