The entered heating-water condition represents 1000000 Btu/h.
Important limitations
Use measured density and specific heat for glycol or unusual temperature. Confirm flow-meter and temperature-sensor uncertainty.
Engineering knowledge center
Understand the calculation—not just the answer
2026-08-07 · Free Library
Governing relationships
Qh = Qw·F·ΔT
Current substitution
Qh = 100×500×20 = 1000000 Btu/h.
Calculation sequence
Step-by-step method
Confirm the fluid-property factor and temperature-difference sign convention.
Multiply flow by factor and temperature difference.
Compare with the applicable operating-point requirement.
Equation legend
Inputs and calculated quantities
Qw
Heating-water flow — gpm or L/s
ΔT
Water temperature difference — °F or K
F
Entered fluid heat-transfer factor — Btu/(h·gpm·°F) or kW/(L/s·K)
Qh
Calculated heating-water capacity — Btu/h
Qw
Entered water flow — gpm
ΔT
Entered temperature difference — °F
F
Entered fluid factor — Btu/(h·gpm·°F)
Applications
How this calculation is used
Building design
Relate design water flow and temperature difference to heating load.
Construction
Check scheduled heating-water conditions.
Commissioning
Estimate field heating capacity with an explicit fluid-property factor.
Quality controls
Assumptions and limitations
Assumptions
Entered values represent one stable operating condition and use consistent measurement boundaries.
Fluid and air properties are representative of the evaluated condition.
Limitations
This is a preliminary evaluation and field-verification tool, not a final sizing or code-compliance determination.
Manufacturer data, adopted codes, project criteria, and professional engineering review remain controlling.
Field use
Verification procedure
Confirm measurement boundaries, operating mode, and instrument calibration.
Stabilize the system and record simultaneous readings.
Compare the calculation with project requirements and manufacturer data before disposition.
Common engineering mistakes
Mixing values from different operating conditions.
Using nominal rather than measured flow, temperature, power, or fluid properties.
Technical basis
References and source standards
ASHRAE Handbook—FundamentalsPsychrometrics, heat transfer, load relationships, and HVAC calculation context; verify the licensed current edition during professional review.
These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.