MechanicalBeginnerDuct Systems

Round Duct Sizing Calculator

Calculate a preliminary round duct diameter from airflow and target average velocity.

Why it matters: Duct area and velocity affect pressure loss, acoustics, coordination, and the quality of airflow measurements.

User inputs

Enter field measurements

4 inputs
Select I-P or SI units. Unit-dependent entries are converted when the selection changes.
cfm or m³/sScheduled or measured volumetric airflow.
fpm or m/sProject-specific target average velocity.
fpm or m/sUser-entered project screening criterion. The calculator does not prescribe a universal duct-velocity limit.

Calculated result

Engineering evaluation

Entered velocity criterion met
Preliminary round duct diameter (D)24.72 in.
Required clear area (A)
3.333 ft²
Entered target velocity (V)
1,500 fpm
Maximum acceptable velocity (Vmax)
2,500 fpm

Engineering interpretation

The entered airflow and velocity require 3.333 ft², equivalent to a preliminary clear round diameter of 24.72 in..

Important limitations

  • Select an available duct size and then recalculate actual velocity, friction, fittings, leakage, acoustics, and construction requirements.

Engineering knowledge center

Understand the calculation—not just the answer

2026-08-07 · Free Library
Governing relationships
A = Q/V
D = 12√(4A/π)
criterion V≤Vmax
Current substitution

A = 5000/1500 = 3.333 ft²; D = 24.72 in.; 1500 ≤ 2500 fpm.

Calculation sequence

Step-by-step method

  1. Divide airflow by target velocity for clear area.
  2. Solve the circular area relationship for diameter.
  3. Convert diameter to millimetres or inches.

Equation legend

Inputs and calculated quantities

Q
Airflow — cfm or m³/s
V
Target average velocity — fpm or m/s
Vmax
Maximum acceptable velocity — fpm or m/s
D
Preliminary round duct diameter — in.
A
Required clear area — ft²
V
Entered target velocity — fpm
Vmax
Maximum acceptable velocity — fpm

Engineering calculation disclaimer

These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.