MechanicalIntermediatePsychrometrics

Surface Condensation-Risk Calculator

Calculate the surface-temperature margin above air dew point from dry-bulb temperature and relative humidity.

Why it matters: A surface at or below dew point is vulnerable to condensation.

User inputs

Enter field measurements

5 inputs
Select I-P or SI units. Unit-dependent entries are converted when the selection changes.
°F or °CRepresentative local air temperature.
%Representative local relative humidity.
°F or °CMeasured or calculated surface temperature.
°F or KProject-specific minimum margin.

Calculated result

Engineering evaluation

Entered dew-point margin met
Surface-above-dew-point margin (M)4.953 °F
Calculated air dew point (Tdp)
55.05 °F
Margin relative to requirement (Mdef)
1.953 °F

Engineering interpretation

The surface is 4.953 °F above the calculated dew point, 1.953 °F relative to the entered margin.

Important limitations

  • Check worst-case humidity, air leakage, thermal bridges, vapor barriers, supports, joints, and sensor uncertainty.

Engineering knowledge center

Understand the calculation—not just the answer

2026-08-07 · Free Library
Governing relationships
Tdp = f(Tdb,RH)
M = Ts−Tdp
Mdef = M−Mreq
Current substitution

Tdp = 55.05; M = 60−55.05 = 4.953; Mdef = 4.953−3 = 1.953.

Calculation sequence

Step-by-step method

  1. Calculate dew point from local dry-bulb and relative humidity.
  2. Subtract dew point from surface temperature.
  3. Compare the margin with the entered requirement.

Equation legend

Inputs and calculated quantities

Tdb
Air dry-bulb temperature — °F or °C
RH
Air relative humidity — %
Ts
Surface temperature — °F or °C
Mreq
Required surface-above-dew-point margin — °F or K
M
Surface-above-dew-point margin — °F
Tdp
Calculated air dew point — °F
Mdef
Margin relative to requirement — °F

Engineering calculation disclaimer

These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.

Read the full use and limitation statement