Calculate CT ratio, PT ratio, combined multiplier, and primary power or energy from an unscaled secondary reading.
Why it matters: An incorrect ratio or a multiplier applied twice can create large commissioning and billing errors.
ΣCALCULATE · VERIFY · INTERPRET
Calculated result
Engineering evaluation
Calculation complete—verify project criteria
Scaled primary quantity (Mᵖ)4,800 matching primary power or energy unit
CT ratio (Kᶜᵗ)
120 ratio
PT ratio (Kᵖᵗ)
4 ratio
Combined multiplier (K)
480 ratio
Engineering interpretation
The entered CT/PT ratios produce multiplier 480 and scaled primary quantity 4800.
Important limitations
Do not apply this combined multiplier to current-only or voltage-only readings. Confirm meter internal scaling, polarity, phase mapping, burden, accuracy, and configuration.
Multiply the ratios for a power or energy multiplier.
Apply the multiplier only to a genuinely unscaled secondary power or energy reading.
Equation legend
Inputs and calculated quantities
CTᵖ
CT primary rating — A
CTˢ
CT secondary rating — A
PTᵖ
PT primary rating — V
PTˢ
PT secondary rating — V
Mˢ
Unscaled secondary reading — kW, kWh, or matching unit
Mᵖ
Scaled primary quantity — matching primary power or energy unit
Kᶜᵗ
CT ratio — ratio
Kᵖᵗ
PT ratio — ratio
K
Combined multiplier — ratio
Applications
How this calculation is used
Building design
Document intended instrument-transformer ratios.
Construction
Check nameplates, polarity, wiring, and meter configuration.
Commissioning
Reconcile an unscaled secondary kW or kWh reading with the primary quantity.
Quality controls
Assumptions and limitations
Assumptions
The entered meter value is genuinely unscaled and requires both CT and PT ratios.
Polarity, phase mapping, wiring, and ratio nameplates are correct.
Limitations
Do not apply the combined multiplier to current-only or voltage-only readings.
Meter internal scaling, pulse constants, billing configuration, accuracy class, and instrument-transformer burden require qualified review.
Field use
Verification procedure
Follow the approved electrical-safety program and use correctly rated instruments.
Confirm wiring, ratios, units, operating mode, and measurement boundaries.
Document simultaneous readings and compare with approved project and manufacturer data.
Common engineering mistakes
Combining values from different time intervals, phases, or measurement boundaries.
Treating a screening result as equipment selection, protective-device coordination, or code compliance.
Technical basis
References and source standards
IEEE Standards AssociationPower quantity, harmonic, transformer, motor, battery, and metering standards; verify the current applicable edition during professional review.
These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.