Calculation sequence
Step-by-step method
- Use line-to-line RMS voltage and representative line current.
- Calculate apparent power using √3VI.
- Multiply apparent power by true power factor to obtain real power.
Calculate balanced three-phase real, apparent, and reactive power from line voltage, line current, and true power factor.
Why it matters: kW and kVA are not interchangeable. The distinction affects loading, generator capacity, transformer utilization, and equipment performance.
Calculated result
The entered balanced three-phase measurements represent approximately 74.8 kW and 83.1 kVA. For unbalanced or distorted systems, use a three-phase power analyzer and evaluate each phase.
Engineering knowledge center
P = √3 × VLL × I × PF / 1000 = √3 × 480 × 100 × 0.9 / 1000 = 74.8 kW.
Calculation sequence
Equation legend
Applications
Screen balanced three-phase load relationships.
Check startup readings against equipment and distribution expectations.
Evaluate measured electrical loading using a true three-phase power analyzer.
Quality controls
Field use
Technical basis
These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.
Read the full use and limitation statement