Estimate flow through a fixed differential-pressure device from a known reference flow and pressure drop.
Why it matters: For a fixed device and fluid condition, flow varies approximately with the square root of differential pressure.
ΣCALCULATE · VERIFY · INTERPRET
Calculated result
Engineering evaluation
Square-root projection requires review
Estimated flow (Q2)150 gpm
Differential-pressure ratio (rΔP)
2.25 ratio
Flow ratio (rQ)
1.5 ratio
Engineering interpretation
For the same fixed device and fluid condition, 9 psi corresponds to an estimated 150 gpm from the entered reference point.
Important limitations
This result projects from the reference point. Verify the relationship with manufacturer or calibrated-device data for the same device position, fluid density, and flow regime.
Engineering knowledge center
Understand the calculation—not just the answer
2026-08-07 · Free Library
Governing relationships
rΔP = ΔP2/ΔP1
rQ = √rΔP
Q2 = Q1√(ΔP2/ΔP1)
Current substitution
rΔP = 9/4 = 2.25; Q2 = 100√2.25 = 150 gpm.
Calculation sequence
Step-by-step method
Divide measured differential pressure by the reference differential pressure.
Take the square root of the pressure ratio.
Multiply reference flow by the square-root ratio.
Equation legend
Inputs and calculated quantities
Q1
Reference flow — gpm or L/s
ΔP1
Reference pressure drop — psi or kPa
ΔP2
Measured pressure drop — psi or kPa
Q2
Estimated flow — gpm
rΔP
Differential-pressure ratio — ratio
rQ
Flow ratio — ratio
Applications
How this calculation is used
Building design
Screen a flow relationship for a fixed valve, coil, or calibrated device.
Construction
Estimate flow from field differential pressure when approved reference data are available.
Commissioning
Reconcile measured differential pressure with the device's known flow-pressure point.
Quality controls
Assumptions and limitations
Assumptions
Entered values describe the same stable operating condition.
Units, pressure definitions, fluid properties, and equipment boundaries are applied consistently.
Limitations
This tool supports preliminary evaluation and field verification; it does not replace manufacturer curves or project-specific engineering analysis.
Project criteria, applicable standards, measurement uncertainty, and authorized professional judgment remain controlling.
Field use
Verification procedure
Confirm the approved reference condition, instrument range, and calculation boundary.
Stabilize the system and record calibrated field measurements.
Compare the result with current manufacturer data and project requirements before disposition.
Common engineering mistakes
Mixing measurements from different operating conditions or equipment boundaries.
Treating a calculated screening status as automatic acceptance.
Technical basis
References and source standards
ASHRAE Handbook—FundamentalsCurrent handbook chapters covering fluid flow, pressure relationships, system curves, and mechanical-system fundamentals; the licensed edition must be verified during professional review.
These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.