MechanicalIntermediateHydronics

Valve Authority Calculator

Calculate control-valve authority from valve pressure drop and the pressure drop of the remaining controlled circuit.

Why it matters: Low valve authority can reduce controllability even when the valve has sufficient nominal flow capacity.

User inputs

Enter field measurements

4 inputs
Select I-P or SI units. Numeric entries are converted when the selection changes.
psi or kPaPressure drop across the fully open control valve at design flow.
psi or kPaPressure drop of the remainder of the controlled circuit at the same flow.
ratioProject-specific screening criterion; the calculator does not prescribe one.

Calculated result

Engineering evaluation

Entered authority criterion met
Calculated valve authority (a)0.333 ratio
Valve share of controlled-circuit drop (100a)
33.33 %
Total controlled-circuit drop (ΔPtotal)
15 psi
Valve drop required for entered minimum (ΔPv,req)
3.333 psi

Engineering interpretation

Calculated valve authority is 0.3333 (33.33%). The entered minimum is 0.25; at the entered remaining-circuit drop, that criterion corresponds to 3.333 psi across the valve.

Important limitations

  • Authority alone does not confirm valve sizing, rangeability, inherent characteristic, actuator authority, minimum differential pressure, or control stability.

Engineering knowledge center

Understand the calculation—not just the answer

2026-08-07 · Free Library
Governing relationships
ΔPtotal = ΔPv+ΔPc
a = ΔPv/ΔPtotal
100a = 100×a
ΔPv,req = amin·ΔPc/(1−amin)
Current substitution

a = 5/(5+10) = 0.3333; ΔPv,req = 3.333 psi.

Calculation sequence

Step-by-step method

  1. Add valve pressure drop to the remaining controlled-circuit pressure drop.
  2. Divide valve pressure drop by the total.
  3. Compare calculated authority with the user-entered minimum criterion.

Equation legend

Inputs and calculated quantities

ΔPv
Design valve pressure drop — psi or kPa
ΔPc
Remaining controlled-circuit drop — psi or kPa
amin
Entered minimum authority — ratio
a
Calculated valve authority — ratio
100a
Valve share of controlled-circuit drop — %
ΔPtotal
Total controlled-circuit drop — psi
ΔPv,req
Valve drop required for entered minimum — psi

Engineering calculation disclaimer

These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.

Read the full use and limitation statement