Calculation sequence
Step-by-step method
- Calculate real-power loading from measured kW and rated kW.
- Calculate apparent-power loading and power factor.
- Multiply measured kW by duration and compare with the entered test screen.
Calculate generator real- and apparent-power loading, power factor, and test energy.
Why it matters: A generator test should identify both kW and kVA loading, duration, power factor, and the approved test criterion.
Calculated result
The test step represents 80% real-power loading and 74.63% apparent-power loading at power factor 0.8571 for 2 hours. The status compares those values with the entered 80% minimum, 100% maximum real-power loading, and 100% maximum apparent-power loading. Final disposition requires the approved generator test procedure and stable frequency, voltage, temperature, and alarm evidence.
Engineering knowledge center
LkW = 600/750×100 = 80%; LkVA = 700/938×100 = 74.63%; E = 1200 kWh.
Calculation sequence
Equation legend
Applications
Screen generator utilization under planned test steps.
Prepare load-bank and integrated-system test records.
Document measured loading and duration against entered requirements.
Quality controls
Field use
Technical basis
These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.
Read the full use and limitation statement