Calculate airflow required for a sensible load using temperature difference and a user-entered air constant.
Why it matters: The required airflow depends on the actual load, temperature difference, and air properties.
ΣCALCULATE · VERIFY · INTERPRET
Calculated result
Engineering evaluation
Calculation complete
Required airflow (Q)5,000 cfm
Entered sensible load (Qs)
108,000 Btu/h
Entered air temperature difference (ΔT)
20 °F
Entered air constant (C)
1.08 Btu/(h·cfm·°F)
Engineering interpretation
The entered sensible duty requires approximately 5000 cfm.
Important limitations
Latent load, ventilation, pressurization, minimum airflow, equipment selection, altitude, and acoustics may govern instead.
Engineering knowledge center
Understand the calculation—not just the answer
2026-08-07 · Free Library
Governing relationships
Q = Qs/(C·ΔT)
Current substitution
Q = 108000/(1.08×20) = 5000 cfm.
Calculation sequence
Step-by-step method
Confirm the sensible-load boundary and target temperature difference.
Select an air-property constant for the operating condition.
Divide load by constant times temperature difference.
Equation legend
Inputs and calculated quantities
Qs
Sensible load — Btu/h or kW
ΔT
Air temperature difference — °F or K
C
Entered sensible-heat air constant — Btu/(h·cfm·°F) or kW/(m³/s·K)
Q
Required airflow — cfm
Qs
Entered sensible load — Btu/h
ΔT
Entered air temperature difference — °F
C
Entered air constant — Btu/(h·cfm·°F)
Applications
How this calculation is used
Building design
Screen airflow for a sensible heating or cooling duty.
Construction
Compare equipment airflow with the entered load basis.
Commissioning
Relate measured sensible load and temperature difference to required airflow.
Quality controls
Assumptions and limitations
Assumptions
Entered values represent one stable operating condition and use consistent measurement boundaries.
Fluid and air properties are representative of the evaluated condition.
Limitations
This is a preliminary evaluation and field-verification tool, not a final sizing or code-compliance determination.
Manufacturer data, adopted codes, project criteria, and professional engineering review remain controlling.
Field use
Verification procedure
Confirm measurement boundaries, operating mode, and instrument calibration.
Stabilize the system and record simultaneous readings.
Compare the calculation with project requirements and manufacturer data before disposition.
Common engineering mistakes
Mixing values from different operating conditions.
Using nominal rather than measured flow, temperature, power, or fluid properties.
Technical basis
References and source standards
ASHRAE Handbook—FundamentalsPsychrometrics, heat transfer, load relationships, and HVAC calculation context; verify the licensed current edition during professional review.
These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.