Calculated result
Engineering evaluation Engineering review recommended Sensor span error (Esp) -4 %
Low-point offset (Olo) 2 selected units
High-point offset (Ohi) -2 selected units Engineering interpretation The two-point check gives -4% span error versus the entered 2% screening tolerance, low offset 2, and high offset -2 in the selected units.
Important limitations Two points do not establish linearity, hysteresis, repeatability, response time, environmental effects, or total uncertainty. Copy results Open printable PDF Download PDF
Report a calculation concern
Engineering knowledge center
Understand the calculation—not just the answer 2026-08-07 · Free Library Equations & method Engineering guide Reference data & sources
Governing relationships Esp = [(Shi−Slo)−(Rhi−Rlo)]/(Rhi−Rlo)×100
Olo = Slo−Rlo
Ohi = Shi−Rhi
compare |Esp| with Tol
Current substitution Esp = [( 98−2)−(100−0)]/(100−0)×100 = -4%; Olo = 2; Ohi = -2; Tol = 2%.
Calculation sequence
Step-by-step method Calculate reference and sensor spans. Compare absolute span error with the user-entered screening tolerance. Calculate low- and high-point offsets. Equation legend
Inputs and calculated quantities
Rlo Reference low point — selected units
Rhi Reference high point — selected units
Slo Sensor low reading — selected units
Shi Sensor high reading — selected units
Tol Entered allowable span error — %
Esp Sensor span error — %
Olo Low-point offset — selected units
Ohi High-point offset — selected units Applications
How this calculation is used Building design Define sensor range and accuracy requirements.
Construction Check wiring, scaling, and installation.
Commissioning Evaluate sensor offset and span against traceable reference readings.
Quality controls
Assumptions and limitations Assumptions Entered data describe one stable operating condition and use consistent measurement boundaries. Time, energy, and performance values are representative of the stated interval. Limitations This is a preliminary evaluation and commissioning-support tool, not an automatic acceptance determination. Project sequences, manufacturer data, tariffs, codes, and professional review remain controlling. Field use
Verification procedure Confirm the operating mode, test boundary, and instrument calibration. Collect simultaneous readings or a documented trend interval. Compare the result with the approved sequence, submittal, and project criteria. Common engineering mistakes Combining measurements from different operating modes or time intervals. Ignoring sensor uncertainty, trend sampling, or the defined equipment boundary. Technical basis
References and source standards Need project-specific support?
Work with SVE Group Use this free tool for preliminary evaluation and field support. For project requirements, system analysis, commissioning, or engineering services, connect with SVE Group.
Visit SVE Group Contact the firm Engineering calculation disclaimer These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.
Read the full use and limitation statement