ElectricalIntermediateConductors and Circuits

Voltage-Drop Calculator

Estimate single-phase or balanced three-phase voltage drop using a transparent conductor reference, resistance-only estimate, or project-specific AC impedance data.

Why it matters: Excessive drop can impair starting, controls, lighting, and equipment performance even when ampacity is adequate.

User inputs

Enter field measurements

13 inputs
Choose the conductor-data methodSelections update the active engineering inputs.
Select the unit convention used for all values in this calculation.
Select single-phase/two-wire or balanced three-phase.
VNominal or measured source voltage.
AExpected or measured load current.
ft or mOne-way length from source to load in the selected unit system.
sets/phaseNumber of identical conductors or cable sets in parallel per phase.
Generic conductivity basis used only by the two estimated-data methods.
Select the conductor cross-sectional area used for the resistance estimate.
°CEstimated operating conductor temperature used to adjust resistance from its 20°C reference value.
Select the visible reactance screening assumption. Use the manufacturer-data tab when project values are available.
0–1Use displacement power factor for the impedance-angle calculation.
Lagging adds the X sin φ term; leading subtracts it.
%Enter the project-specific review criterion; the calculator does not impose a code limit.

Calculated result

Engineering evaluation

Within entered screening limit
Estimated voltage drop (ΔV)5.38 V
Voltage drop (ΔV%)
1.12 %
Estimated load voltage (VL)
475 V
Conductor resistance used (Rc)
0.12 Ω/1,000 ft
Conductor reactance used (Xc)
0.05 Ω/1,000 ft
Parallel conductor sets (n)
1 sets/phase
Conductor area (Acond)
53.48 mm²
Circuit multiplier (k)
1.732
Power factor (PF)
0.9
Effective R cos φ component (Reff cos φ)
0.108 Ω/1,000 ft
Lagging effective X sin φ component (Xeff sin φ)
0.022 Ω/1,000 ft
Entered screening limit (ΔVlimit)
3 %

Engineering interpretation

Estimated load voltage is 475 V, a 1.12% change from the entered source voltage. The calculation used the conductor reference method with 1 parallel set per phase. The 3% comparison is a user-entered screening criterion, not conductor-selection or code-compliance certification.

Important limitations

  • Estimated conductor data is a transparent screening basis, not an electrical-code table or manufacturer product value. Confirm stranding, material, temperature, frequency, cable geometry, raceway, and installed impedance before final design.
  • The equation assumes a balanced sinusoidal circuit and user-entered conductor impedance at the applicable frequency and temperature. Harmonics, parallel-path current sharing, and connection resistance require separate evaluation.

Engineering knowledge center

Understand the calculation—not just the answer

2026-08-08 · Enhanced review build
Circuit voltage-drop equationΔV=3IL(Rccosφ+Xcsinφ)1000n
Percent voltage dropΔV%=ΔVVs×100
Estimated load voltageVL=Vs−ΔV
Conductor-data relationshipRc(Tc)=ρ201000Acond[1+α20(Tc−20)]
Current substitution

ΔV = 1.732 × 80 × 300 ft × [(0.11951 ÷ 1) × 0.9 + (0.05 ÷ 1) × 0.43589] Ω/1,000 ft / 1000 = 5.38 V; ΔV% = 1.12%.

Calculation sequence

Step-by-step method

  1. Derive conductor resistance from material, area Acond, and entered temperature Tc; use the selected visible reactance assumption.
  2. Divide single-conductor resistance and reactance by the number of equal parallel sets per phase.
  3. Resolve effective impedance along the load-current angle using Reff cos φ and Xeff sin φ; subtract the reactive term for a leading load.
  4. Apply the balanced three-phase circuit multiplier.
  5. Divide calculated drop by source voltage and compare it only with the user-entered screening limit.

Equation legend

Inputs and calculated quantities

Vs
Source voltage — V
I
Load current — A
L
One-way circuit length — ft or m
n
Parallel conductor sets — sets/phase
Tc
Conductor temperature — °C
PF
Displacement power factor — 0–1
ΔVlimit
Project screening limit — %
ΔV
Estimated voltage drop — V
ΔV%
Voltage drop — %
VL
Estimated load voltage — V
Rc
Conductor resistance used — Ω/1,000 ft
Xc
Conductor reactance used — Ω/1,000 ft
n
Parallel conductor sets — sets/phase
Acond
Conductor area — mm²
k
Circuit multiplier
PF
Power factor
Reff cos φ
Effective R cos φ component — Ω/1,000 ft
Xeff sin φ
Lagging effective X sin φ component — Ω/1,000 ft
ΔVlimit
Entered screening limit — %

Engineering calculation disclaimer

These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.

Read the full use and limitation statement