ElectricalAdvancedShort-Circuit Screening

Transformer Secondary Fault-Current Screening Calculator

Estimate transformer-limited balanced three-phase secondary fault current from rating, voltage, and nameplate impedance.

Why it matters: The simple transformer limit is useful for orientation but is not a short-circuit, coordination, or arc-flash study.

User inputs

Enter field measurements

4 inputs
Select I-P or SI display units. Electrical units remain unchanged unless a real conversion is identified.
kVAThree-phase transformer nameplate rating.
VNameplate or applicable secondary line-to-line voltage.
%Nameplate percent impedance on the transformer rating base.

Calculated result

Engineering evaluation

Calculation complete—verify project criteria
Transformer-limited fault-current screen (Iˢᶜ)10.459 kA
Full-load secondary current (Iᶠˡ)
601.407 A
Transformer fault multiplier (Mᶠ)
17.391 ratio

Engineering interpretation

The transformer-only ideal screen is 10.45924 kA at the secondary terminals under the stated assumptions.

Important limitations

  • Transformer-limited screening only. Never use this result as an interrupting rating, coordination result, incident energy, arc-flash result, available downstream fault current, or code-compliance determination.
  • A formal study must include source and conductor impedance, motors, parallel sources, X/R, tolerances, grounding, and protective devices.

Engineering knowledge center

Understand the calculation—not just the answer

2026-08-07 · Free Library
Governing relationships
Iᶠˡ = 1000Sᵀ/(√3·Vᴸᴸ)
Mᶠ = 100/Z%
Iˢᶜ = Iᶠˡ·Mᶠ/1000
Current substitution

Iᶠˡ = 1000×500/(√3×480) = 601.4065 A; Mᶠ = 100/5.75 = 17.3913; Iˢᶜ = 10.45924 kA.

Calculation sequence

Step-by-step method

  1. Calculate balanced transformer full-load secondary current.
  2. Divide 100 by nameplate percent impedance.
  3. Multiply and convert amperes to kA.

Equation legend

Inputs and calculated quantities

Sᵀ
Transformer rating — kVA
Vᴸᴸ
Secondary line voltage — V
Z%
Transformer impedance — %
Iˢᶜ
Transformer-limited fault-current screen — kA
Iᶠˡ
Full-load secondary current — A
Mᶠ
Transformer fault multiplier — ratio

Engineering calculation disclaimer

These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.

Read the full use and limitation statement