ElectricalIntermediateElectrical Fundamentals

AC Power Triangle Calculator

Reconcile signed real and reactive power into apparent power, power-factor magnitude, and power angle.

Why it matters: The signed reactive-power convention distinguishes lagging from leading operation while preserving the measured apparent-power relationship.

User inputs

Enter field measurements

3 inputs
Select I-P or SI display units. Electrical units remain unchanged unless a real conversion is identified.
kWSigned real power; negative values may represent export or generation.
kvarPositive kvar is lagging; negative kvar is leading.

Calculated result

Engineering evaluation

Calculation complete—verify project criteria
Apparent power (S)100 kVA
Power-factor magnitude (PF)
0.8 0–1
Power angle (φ)
36.87 degrees

Engineering interpretation

The entered powers yield 100 kVA at PF 0.8 and angle 36.8699°. Positive kvar is lagging; negative kvar is leading.

Important limitations

  • Nonsinusoidal conditions may require additional IEEE 1459 power quantities.

Engineering knowledge center

Understand the calculation—not just the answer

2026-08-07 · Free Library
Governing relationships
S = √(P²+Q²)
PF = |P|/S
φ = atan2(Q,P)
Q>0 lagging
Q<0 leading
Current substitution

S = √(80²+60²) = 100 kVA; PF = |80|/100 = 0.8; φ = 36.8699°.

Calculation sequence

Step-by-step method

  1. Combine real and signed reactive power by root-sum-square.
  2. Divide absolute real power by apparent power.
  3. Use signed kvar to preserve leading or lagging angle.

Equation legend

Inputs and calculated quantities

P
Real power — kW
Q
Signed reactive power — kvar
S
Apparent power — kVA
PF
Power-factor magnitude — 0–1
φ
Power angle — degrees

Engineering calculation disclaimer

These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.

Read the full use and limitation statement