Calculated result
Engineering evaluation Calculation complete—verify project criteria Real power (P) 3.84 kW
Apparent power (S) 4.8 kVA
Reactive-power magnitude (Q) 2.88 kvar Engineering interpretation The entered single-phase condition represents 3.84 kW, 4.8 kVA, and 2.88 kvar magnitude.
Important limitations Reactive-power direction is not inferred. Confirm leading or lagging operation and use true-power instrumentation for distorted waveforms. Copy results Open printable PDF Download PDF
Report a calculation concern
Engineering knowledge center
Understand the calculation—not just the answer 2026-08-07 · Free Library Equations & method Engineering guide Reference data & sources
Governing relationships S = V·I/1000
P = S·PF
Q = S√(1−PF²)
Current substitution S = 240×20/1000 = 4.8 kVA; P = 4.8×0.8 = 3.84 kW; Q = 2.88 kvar.
Calculation sequence
Step-by-step method Multiply RMS voltage by RMS current for apparent power. Apply true power factor for real power. Calculate reactive-power magnitude from the power triangle. Equation legend
Inputs and calculated quantities
V RMS voltage — V
I RMS current — A
PF True power factor — 0–1
P Real power — kW
S Apparent power — kVA
Q Reactive-power magnitude — kvar Applications
How this calculation is used Building design Screen single-phase load relationships.
Construction Reconcile startup voltage, current, and power readings.
Commissioning Check a measured single-phase operating point using true RMS values and true power factor.
Quality controls
Assumptions and limitations Assumptions Entered values describe one stable operating condition and use a consistent electrical or metering boundary. Measured quantities are simultaneous, representative, and obtained with appropriately rated instruments. Limitations Reactive power is reported as a magnitude unless the leading or lagging direction is separately known. Distorted waveforms require a true-power analyzer and appropriate power-quantity definitions. Field use
Verification procedure Follow the approved electrical-safety program and use correctly rated instruments. Confirm wiring, ratios, units, operating mode, and measurement boundaries. Document simultaneous readings and compare with approved project and manufacturer data. Common engineering mistakes Combining values from different time intervals, phases, or measurement boundaries. Treating a screening result as equipment selection, protective-device coordination, or code compliance. Technical basis
References and source standards Need project-specific support?
Work with SVE Group Use this free tool for preliminary evaluation and field support. For project requirements, system analysis, commissioning, or engineering services, connect with SVE Group.
Visit SVE Group Contact the firm Engineering calculation disclaimer These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.
Read the full use and limitation statement