Calculate ideal minimum amp-hour capacity for a constant AC load and required runtime.
Why it matters: The ideal inverse energy balance is useful for early planning but is not a selected battery string.
ΣCALCULATE · VERIFY · INTERPRET
Calculated result
Engineering evaluation
Calculation complete—verify project criteria
Ideal required battery capacity (Cʳ)57.87 Ah
Required nominal energy (Eʳ)
13.889 kWh
Engineering interpretation
The ideal screen requires 13.88889 kWh nominal energy or 57.87037 Ah at 240 V DC.
Important limitations
Ideal screening only. Exact manufacturer discharge data are mandatory for final use; do not round down or treat this value as a selected battery string.
Divide by user-entered efficiency and usable depth.
Convert nominal energy to ideal amp-hour capacity.
Equation legend
Inputs and calculated quantities
Pᴸ
AC load — kW
t
Required runtime — h
Vᴰᶜ
Nominal DC voltage — V
η
UPS/inverter efficiency — %
DOD
Usable depth of discharge — %
Cʳ
Ideal required battery capacity — Ah
Eʳ
Required nominal energy — kWh
Applications
How this calculation is used
Building design
Screen required nominal energy and Ah.
Construction
Check load, runtime, voltage, and efficiency assumptions.
Commissioning
Compare the ideal requirement with manufacturer selection and test data.
Quality controls
Assumptions and limitations
Assumptions
Constant load and nominal voltage for the ideal screen.
Entered efficiency and usable depth apply over the full interval.
Limitations
Ideal screening only; exact manufacturer discharge data are mandatory for final use.
Cell count, end voltage, temperature, aging margin, duty cycle, recharge, redundancy, and selection rules are omitted.
Field use
Verification procedure
Follow the approved electrical-safety program and use correctly rated instruments.
Confirm wiring, ratios, units, operating mode, and measurement boundaries.
Document simultaneous readings and compare with approved project and manufacturer data.
Common engineering mistakes
Combining values from different time intervals, phases, or measurement boundaries.
Treating a screening result as equipment selection, protective-device coordination, or code compliance.
Technical basis
References and source standards
IEEE Standards AssociationPower quantity, harmonic, transformer, motor, battery, and metering standards; verify the current applicable edition during professional review.
These engineering tools are provided for educational, preliminary evaluation, field verification, and commissioning support. Results depend on the accuracy of user-entered information and the assumptions stated for each calculation. Every colored status and comparison is a screening indicator only; project criteria, contract requirements, applicable codes, manufacturer instructions, measurement uncertainty, and authorized engineering judgment govern. The tools do not replace project-specific engineering analysis or the judgment of a licensed professional engineer.